GRP Underground Petroleum Tank
Tank shall meet the following design criteria:
1. External Hydrostatic Pressure
Buried underground with two( 2) meters overburden over the top of the tank. The hole fully flooded and a safety factor of 2:1 against buckling.
2. Surface Loads
When installed according to our installation instructions, tank shall withstand a total external load of two( 2) meters cover on top of the tank plus a concentrated load of 10,169 kgs.
3. Internal Loads
Tank shall withstand 3- 5 psig internal pressure with 5: 1 safety factor. |
|
Tank Fabrication Materials
1. Resin
The resin system to be used is a commercial grade, corrosion- resistant and inert to the petroleum products to be stored.
2. Reinforcing Materials
Fiberglass reinforcements shall be a combination of continuous roving and chopped stand mat and woven roving of the “E” glass type. Innermost layer in contact with the stored liquid shall be reinforced with a surface veil of the “C” glass type.
|
|
GRP Underground Petroleum Tanks are UL-listed, light-weight and easy to install
|
Underground Petroleum Tanks are UL-listed,light-weight
and easy to install.
.
(1) Laid flat on ground,fully- filled with water.
(2) then,pressurized to 25 psig…
…then backfilled and pit flooded until water overflows…
… While buried, tank subjected to vacuum pressure of 173.75 mmHg under watchful eye of Underwriters Laboratory’s (UL) representative…
Standard dimensions |
Capacity
(Liters)
|
Diameter, f
(mm)
|
Cylinder Length, CYL (mm)
|
Endcap Height
CH (mm)
|
Dimensions
(mm)
|
4,000
|
1600
|
1812
|
200
|
1600f x 2212L
|
5,000
|
1600
|
2309
|
200
|
1600f x 2709L
|
6,000
|
1600
|
2806
|
200
|
1600f x 3206L
|
7,000
|
1600
|
3304
|
200
|
1600f x 3704L
|
8,000
|
1600
|
3801
|
200
|
1600f x 4201L
|
9,000
|
1600
|
4299
|
200
|
1600f x 4699L
|
10,000
|
1600
|
4796
|
200
|
1600f x 5196L
|
11,000
|
2000
|
2196
|
1000
|
2000f x 4195L
|
12,000
|
2000
|
2513
|
1000
|
2000f x 4513L
|
13,000
|
2000
|
2831
|
1000
|
2000f x 4831L
|
14,000
|
2000
|
3149
|
1000
|
2000f x 5149L
|
15,000
|
2400
|
3468
|
1000
|
2400f x 5468L
|
20,000
|
2400
|
3216
|
1000
|
2400f x 5216L
|
25,000
|
2400
|
4321
|
1000
|
2400f x 6321L
|
30,000
|
2400
|
5426
|
1000
|
2400f x 7426L
|
35,000
|
2400
|
6532
|
1000
|
2400f x 8532L
|
40,000
|
2400
|
7637
|
1000
|
2400f x 9637L
|
45,000
|
2400
|
8742
|
1000
|
2400f x 10742L
|
50,000
|
3000
|
5644
|
1200
|
3000f x 8044L
|
55,000
|
3000
|
6351
|
1200
|
3000f x 8751L
|
60,000
|
3000
|
7059
|
1200
|
3000f x 9459L
|
65,000
|
3000
|
7766
|
1200
|
3000f x 10166L
|
70,000
|
3000
|
8473
|
1200
|
3000f x 10873L
|
75,000
|
3000
|
9181
|
1200
|
3000f x 11581L
|
80,000
|
3000
|
9888
|
1200
|
3000f x 12288L
|
85,000
|
3000
|
10596
|
1200
|
3000f x 12996L
|
90,000
|
3000
|
11303
|
1200
|
3000f x 13703L
|
|
Liters capacity underground petroleum tanks supplied 48.8000 Liters capacity underground petroleum tanks supplied to KNPC